Residence
Hall Sprinkler Systems
By William Conk
Manager - Housing Facilities and Operations
University of New Hampshire
Introduction
There are
many responsibilities that housing professionals have when providing a
place to live for students. One of the most important is to provide a
safe living environment. Fire safety in the residence halls and apartments
is one of the most fundamental responsibilities.
There are
different components to fire safety. The first component is prevention.
A college or university must have policies and procedures in place that
will minimize the potential that a fire will start in the first place.
This includes such things as fire safety inspections or restricting what
students can use in the residence halls, such as candles, halogen lamps,
hot plates, etc. But for policies to be effective there must be the willingness
to follow through with judicial and even legal action when university
rules and or state laws are broken.
A second
component is maintaining facilities. There must be an emphasis on ensuring
that building deficiencies are identified and, where safety is a factor,
repaired in a timely manner. Particularly important are stairwell door
closures and spring-loaded hinges on student room doors. Fire extinguishers,
exit signs and emergency lighting should also be maintained in constant
working order.
A third
component is a notification system. All residence halls should have two
types of alarm systems. The first is a hardwired smoke detector that should
be located in every student living space. This is a smoke detector that
sounds locally in a student room when activated. The second is a building
fire alarm system with smoke detectors in hallways and common areas and
pull stations at exits which, when activated, will alert occupants of
an emergency and the need to vacate the building.
These three
components of fire safety are basic standards which every college or university
should have in place for their residential housing programs. Most state
and local building codes call for these safety devices and procedures
and there is usually no "grand fathering" of these requirements.
There is
a fourth component that is often not required but which every university
and college should strive for and that is the installation of sprinkler
systems in residential facilities. Traditionally it was identified that
fire alarm notification systems were installed to protect occupants by
notifying occupants of the emergency and warning them to leave the building.
On the other hand, building sprinkler systems were installed to protect
property. Sprinklers systems were designed to control, and possibly suppress
fires when they occurred. The common belief was that the owner could make
his/her own decision on the protection of property. Based on this philosophy
sprinkler systems were not required by local building codes until only
recently and in some instances they are still not required. In most cases,
existing buildings are "grand fathered" and not required to upgrade. Over
time, however, sprinkler systems have proven themselves as an important
component of life safety. By controlling or suppressing fires they minimize
the destructive heat and gases produced by fires and allow occupants time
to escape the building.
Understanding
the Dynamics of the Danger
There are
two very specific things that will cause harm or death to students, smoke
and fire. Fire occurs when you have material to burn, oxygen and a source
of ignition. Smoke is the product of incomplete combustion and will be
evident in any fire situation. Most deaths in a fire situation are caused
by asphyxiation as the result of the inhalation of smoke.
There are
occasional situations of a smoldering fire where, due to the material
burning, flames are not evident but smoke is being released. These situations
are the one's often cited for why money spent on sprinkler systems is
not money effectively spent. It is a very good example of why a fire alarm
system is a critical component of any fire safety program. A smoke detector,
located in a room, would activate and warn occupants and neighbors. Smoke
would eventually creep around the door to activate the building system
and notify all occupants.
However,
most residential fires are not smoldering fires. Residential fires are
full fires that quickly consume all available combustible material and
oxygen and produce extreme amounts of heat and toxic smoke. In a typical
room fire, within thirty seconds of flames initially appearing, on average
the temperature at the ceiling will be over 300 degrees. Within two minutes,
the temperature at the ceiling will be over 1,000 degrees and the floor
temperature will be over 200 degrees. Fires burn hot and they burn very
quickly! They are very fearsome situations resulting in panic, disorientation
and sometimes harm and death.
A sprinkler
head, located in a typical room will activate at approximately 135 degrees.
The design of the sprinkler head and sprinkler system will ensure that
the spray of water will cover the complete room. With an average pressure
of 45 psi a 3/8-inch diameter sprinkler head will disperse a minimum of
18 gallons per minute into the room. Instead of 300 degrees at the ceiling
after 30 seconds, the room is being covered with water that is controlling
the heat and the flames, often suppressing the fire. Instead of injured
students, you most likely will have just soggy students.
Building
Sprinkler Systems
There
are, for general reference, four basic components of sprinkler systems:
- water
supply
- main
distribution
- branch
distribution
- alarm
systems
The water
supply is the water source that will feed the sprinkler system. Generally
code requires that sprinkler systems be fed by a six-inch water main that
comes into a building. There are very few older buildings that were built
with this type of domestic water supply that therefore necessitates that
a new water line will have to be part of a sprinkler upgrade. Unfortunately,
this can sometimes prove to be difficult and costly depending on a building's
location and the water distribution system around campus. If one is lucky,
a water main of sufficient size and pressure will be adjacent to the building.
If one is unfortunate, the water main may be a distance away requiring
considerable site work. A second consideration would be the water entry
location into the building. Minimal space requirements for a sprinkler
water entrance, without pumps, would generally be four feet by eight feet.
This space would permit the piping into the building and the necessary
valving.
The
main distribution system throughout the building is basically the vertical
piping system that supplies the water to the different floors. Most
often this is four-inch steel pipe that leaves the water entrance and
rises at some appropriate place in the building. The appropriate place
is really dependent on the building layout and the sprinkler system design.
Ideally, this vertical riser would be in a central location running through
closets that stack on top of each other. Other vertical risers, that will
generally be required, are what are referred to as standpipes. These are
also four inch steel pipes located in one or two stairwells with a valve
at each floor landing which fire fighters can connect hoses to in order
to fight fires. In some designs standpipes can also serve as the central
riser for the sprinkler distribution. Some older buildings, built in the
60's and 70's, had dry standpipes incorporated into the original construction.
Most times these can be used for some cost savings.
The branch
distribution system is basically the horizontal distribution system that
spreads out on each floor to provide the actual sprinkler coverage.
Each floor of the building will be its own zone. If it is a large building
or one of unusual design, two or more zones may be required. The transition
from main distribution to branch distribution is accomplished through
a series of several small valves. These valves should be enclosed behind
a locked closet or inside a locked box, such as you might use in a stairwell.
The piping at this point will decrease in size, generally one to two inch
piping. Here the piping can continue to be steel or it can be a special
type of plastic piping. Steel piping generally must hang, at least several
inches from the ceiling from hangers. Plastic piping can generally be
attached directly to the ceiling. When plastic piping initially came out
in the late 80's the sprinkler industry approached it with great reluctance.
Now its use is as common as steel. Branch distribution is dependent upon
building design and cost considerations. Designs will basically be one
of two types. A main branch will either run down the corridor and branch
into rooms or the main branch will run down the rooms with sprinkler heads
punching out into the corridors. A branch system that can be designed
as a loop system will allow for smaller sized pipe.
At the
University of New Hampshire, where I work in the Department of Housing,
the advent of plastic piping allowed us to approach the installation and
design of branch systems with new options. There were two initial concerns.
The first was not to have piping that residents could hang on. The second
was a concern for aesthetics. Generally, most of our designs have the
branch distribution running inside the student room, on the ceiling along
the wall adjacent to the corridor. Depending on the building and the availability
of funds we have either left this piping exposed or we have built soffits
around the pipe. Attached to the ceiling, in the corner of the ceiling,
painted white to match the ceiling, the piping has a very low visual profile.
Considering the safety factor this added for our residents; this was deemed
an acceptable trade off. Sprinkler heads are then incorporated into this
piping with piping and sprinkler heads going through the corridor wall
to cover the corridor. The actual location of the sprinkler head is dependent
on the design and size of the room. Where a sprinkler head is needed to
be located on a wall adjacent to the neighboring room, that neighboring
room would be covered by going through the wall at that location. This
cuts down on the amount of piping.
The
fourth component is the alarm system. A building sprinkler must be
tied into a building fire alarm system. The activation of a sprinkler
head and flow of water will need to trigger the same response as a smoke
detector activation or someone pulling a pull station. This is accomplished
primarily at the transitions between the main distribution and the branch
distribution. There are electronic devices at these locations that activate
when water flow is initiated. When retrofitting existing buildings the
problem may arise where the existing fire alarm panel does not have sufficient
capacity to accept these new input devices from the sprinkler system.
At best, a new slave panel to the existing panel can be installed to accept
the sprinkler inputs and feed them to the existing panel. If this is not
possible a new fire alarm panel may be required which would significantly
affect the cost of the project.
Sprinkler
System Designs
There are
several avenues to pursue in order to have a sprinkler system designed
for a building.
One avenue
would be to contact a sprinkler contracting company. All sprinkler companies
need to have on staff qualified personal to design sprinkler systems and
produce hydraulic calculations required to meet the approval of the local
fire department or state fire marshal.
A second
avenue would be to hire a mechanical engineering firm to do the design.
This avenue would generally also include the involvement of an architect
who would be able to pay attention to architectural details.
A third
avenue would be to hire a fire safety-engineering firm to design the system.
A fire safety engineer has training in the different disciplines that
are involved in sprinkler system designs. However, fire safety engineers
are generally used for the more complex sprinkler designs involved in
very large and uniquely designed buildings.
My own experience
has led me to favor hiring a firm with both architectural, mechanical
and electrical engineering staff. A design by a sprinkler contracting
firm will often, though not always, be focused on providing the most design
efficient and inexpensive installation possible, often at the expense
of architectural considerations. By incorporating both an architect and
mechanical engineer into the design architectural aesthetic considerations
can be addressed, and inexpensive solutions developed. The fire safety
engineering option often involves considerable costs.
A final
critical factor in the design process is the relationship the university
or college has with the local fire department or state fire marshal who
has final jurisdiction over any design approval. Hopefully, a cooperative
relationship can be developed. At the University of New Hampshire, this
type of cooperative relationship has existed and has greatly facilitated
the design and installation of sprinkler systems. The Durham Fire Department
and State Fire Marshall have been very supportive of the sprinkler program
initiated by the Department of Housing and have demonstrated this support
by considering and approving requests for different design alternatives
that have facilitated installation and lowered cost. For the local jurisdiction
or institution to take uncompromising positions the result will only be
a delay in the installation of sprinkler systems and the protection of
students.
Student
Concerns
There is
often concern about the issue of student vandalism to sprinkler systems
and the accidental activation of a sprinkler head. For these concerns,
I can only respond from ten years experience. When we started installing
sprinkler systems in 1989 I was prepared for a marked increase in the
number of accidental activations of sprinkler heads. Happily, this has
not been our experience. On average, over the past ten years, we maybe
have had one accidental activation a year. Students have been respectful
of the system. It is often the errant frisbee or soccer ball that hits
the head and causes the activation. The cost of this clean up, charged
to the responsible student or students, is well worth the price for the
protection the system provides. There has never in our experience been
any vandalism to the system. With the sprinkler tied into the fire alarm
system, any vandalism will initiate either a trouble signal or an alarm
activation.
On the
other hand, we have had a couple of fires over the years that have been
controlled or completely extinguished by the sprinkler system significantly
reducing the amount of damage to the facility. Most importantly, however,
none of these fires resulted in any injuries or deaths, which, without
the sprinkler system, they very well could have.
There is
also the need to dispel a common misperception of a sprinkler system.
It is a common misperception that when one sprinkler head activates they
all activate. There is also a misperception that sprinklers will activate
when a fire alarm system is activated. Sprinkler heads all activate individually.
In a fire situation heat will result in a fuse or glass bulb, located
in the sprinkler head, breaking which in turn allows the flow of water
only from that individual head. Most times only one or two sprinkler heads
end up activating in a fire situation.
Conclusion
Building
sprinkler systems can and must become part of every residential facility
on college and university campuses, both for new buildings and old buildings.
A sprinkler system is not a complex system and depending on one's concerns
for architectural aesthetics can be installed rather inexpensively. If
college or university officials are not supportive of these initiatives
it is up to the housing and residential life professional staff to become
educated about these systems and actively and relentlessly lobby for these
systems to have priority for the use of funds on the campus. The costs
for these systems will pale in comparison to the costs an institution
will pay if a resident is injured or dies in a fire. Private institutions,
in particular since public facilities are usually self-insured, should
check with their insurance companies for the potential of reduced insurance
premiums.
Finally,
it is always important to see sprinkler systems as only one part of a
comprehensive fire safety system for a residential program. Any one system
can fail. It is the integration of several systems that will provide the
greatest protection to our students and staff living in the residence
halls.
About the Author
William
Conk has worked for 20 years as the Manager - Housing Facilities and Operations
at the University of New Hampshire. In this position, he oversees facilities
planning, major repairs and renovations, maintenance, housekeeping, grounds,
communication systems and technology for the Department of Housing. William
is an advanced Emergency Medical Technician, and volunteers for the Durham
Ambulance Core in New Hampshire, and the Biddleford Free Clinic in Maine.
William also works as a logistical officer for Doctors Without Borders.
William has a Bachelor of Arts degree from Stonehill College and Masters
of Arts degrees from the University of Minnesota.